Addressable Fire Alarm Control Panels

Apollo-Elite-2-loop-Panel-Red-2-1.jpg

Apollo Elite VF1480

The Elite VF1480 analog addressable FACP with networked releasing, supports 2 or 4 SLC loops for a total of 500 primary points and up to 800 points using subpoints. SLC loop communications uses standardtwisted pair cabling, shielded cable is not necessary.

Specifications
Details
Aux Inputs
(3) digital pull downs
Aux Power
500mA @ 24VDC
Voltage Output
(3) 500mA @ 24VDC, reverse polarity supervised
Relay Outputs
(5) Form C 1 Amp @ 30VDC
NAC Outputs
(4) 1.6 Amp @ 24VDC (class B)
Devices perloop
126 sensors & modules (800 addresses + sub-addresses max. per panel)
SLC Loops
2 or 4 (Class A or B)
Zones
500 Zones per network
Display
8 line x 40 character LCD (320 characters total)
Charger Current
1.25 Amps Max
Power Supply
5.25 Amp regulated and intergrated
Output DC
24VDC @ 4 Amps
Primary AC
120VAC @ 2 Amps 60hz (OPtional 240 VAC 50hz)
163721831_m.jpg

灭火控制面板

SigmaA-XT-800x737.jpg

Kentec Sigma A-XT 自动释放控制面板

Kentec Sigma A-XT 是一款高性价比的固定式灭火释放控制面板,适用于中小型灭火系统安装项目。它具备三组标准启动电路,可根据不同需求配置触发逻辑,例如“任意三选二”模式,适用于天花板空间、室内区域与地板夹层等多个火灾探测区域的联合触发控制。

Specification
Details
Battery fuse
20mm, 3.15A glass
Battery charge current
0.7A maximum
Battery charge voltage
27.6VDC nominal (temperature compensated)
Battery Type
Two 12 Volt 7Ah sealed lead acid in series
Maximum ripple current
200 millivolts
Mains supply fuse
1.6Amp (FL.6A L250V)
Power supply rating
3 Amps total including battery charge 28V +/- 2V
Mains supply
230V AC or 115V AC
Colour- lid & box
Red RAL 3002 (optional grey BS 00 A 05 semi-matt)
Finish
Epoxy powder coated
IP rating
IP30
Construction
1.2mm mild sheet steel