Addressable Fire Alarm Control Panels

Apollo Elite VF1480
The Elite VF1480 analog addressable FACP with networked releasing, supports 2 or 4 SLC loops for a total of 500 primary points and up to 800 points using subpoints. SLC loop communications uses standardtwisted pair cabling, shielded cable is not necessary.
Specifications | Details |
---|---|
Aux Inputs | (3) digital pull downs |
Aux Power | 500mA @ 24VDC |
Voltage Output | (3) 500mA @ 24VDC, reverse polarity supervised |
Relay Outputs | (5) Form C 1 Amp @ 30VDC |
NAC Outputs | (4) 1.6 Amp @ 24VDC (class B) |
Devices perloop | 126 sensors & modules (800 addresses + sub-addresses max. per panel) |
SLC Loops | 2 or 4 (Class A or B) |
Zones | 500 Zones per network |
Display | 8 line x 40 character LCD (320 characters total) |
Charger Current | 1.25 Amps Max |
Power Supply | 5.25 Amp regulated and intergrated |
Output DC | 24VDC @ 4 Amps |
Primary AC | 120VAC @ 2 Amps 60hz (OPtional 240 VAC 50hz) |

Gas Releasing Fire Control
Panel Fire

Kentec Sigma A-XT
The Elite VF1480 analog addressable FACP with networked releasing, supports 2 or 4 SLC loops for a total of 500 primary points and up to 800 points using subpoints. SLC loop communications uses standardtwisted pair cabling, shielded cable is not necessary.
UL 864 9th Edition listed
Specification | Details |
---|---|
Aux Inputs | (3) digital pull downs |
Primary AC | 120VAC @ 2 Amps 60hz (OPtional 240 VAC 50hz) |
Output DC | 24VDC @ 4 Amps |
Power Supply | 5.25 Amp regulated and intergrated |
Charger Current | 1.25 Amps Max |
Display | 8 line x 40 character LCD (320 characters total) |
Zones | 500 Zones per network |
SLC Loops | 2 or 4 (Class A or B) |
Devices perloop | 126 sensors & modules (800 addresses + sub-addresses max. per panel) |
NAC Outputs | (4) 1.6 Amp @ 24VDC (class B) |
Relay Outputs | (5) Form C 1 Amp @ 30VDC |
Voltage Output | (3) 500mA @ 24VDC, reverse polarity supervised |
Aux Power | 500mA @ 24VDC |